Permit: T04CM00929

Parcel: 12419025A


Addresses:

1665 E 18TH ST 02

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/23/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*/ 1) SOIL WATER TEST IS OK. 2) P.O.C. OF NEW BLDG DRAIN TO EXISTING BLDG DRAIN IS OK. 3) OK TO BACKFILL TRENCH. 4) SERVICE SINK AT REAR BLDG IS OK.
03/19/2004 PLUMBING - INTERMEDIATE Denied 1) CANNOT HAVE A 2" TRAP ARM FOR LAVATORY MAX. SIZE OF TRAP ARM IS 1 1/2" FOR LAVATORY 2) MUST REMOVE 2 X 1 1/2" SAN TESS FOR VENT AT SERVICE SINK AND ROUGH THIS DRAIN CONVENTIONALLY 3) CAN USE CLEANOUT TEE ON A HORIZONTAL POSITION 4) RE-TEST SYSTEM 5) PLAN WAS APPROVED IN ERROR
03/10/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) MAKE BATHROOM ADA ACCESSABLE. 2) LAVATORY DRAIN LINE MAY NOT DUMP INTO WTR CLOSET VENT. (THIS APPLICATION IS NOT WET VENTING). 3) BOOTLEGGED SERVICE SINK TO BE REMOVED. IF YOU WANT IT TO STAY, PROVIDE APPROVED PLAN FOR INSTALLATION.