Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/16/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/60 AMP BREAKERS TOO LARGE FOR A/C UNITS. 50 AMP IS MAX. CHECKED DUCT SMOKE DETECTORS. RECALL FOR INSPECTION |