Permit: T04CM00851

Parcel: 13419042D

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T04CM00851

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/17/2004 PLUMBING - FINAL Approved IVRS - Inspection :*APPROVED-CORRECTIONS MADE
6 BACKFLOW CERTIFICATIONS TURNED IN.
01090 APPROVED PER LEE RAY. GAS CARD AT METER STUB.
08/16/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :1" AIR GAP FOR ALL INDIRECT DRAINAGES
ESPRESSO DRAINAGE CANNOT TRAP WATER IN PIPING
SINK AT ? THRU TO DRAIN INTO FLOOR SINK WITH 1" AIRGAP
USE APPROVED 2-HOLE STRAPS FOR SECURING PIPING, PLUMBERS TAPE IS NOT AN APPROVED METHOD
08/11/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ COMPLETE ALL WORK THEN CALL FOR INSP. INSTALL DRAINAGE AND H2O PIPING PER PLAN.