Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM00850
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2004 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/30/2004 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PROPERLY TERMINATE GROUNDING CONDUCTORS-IF ISO GRD USE APPROVED ISO BUSS 2) PANEL PARTS TO BE FREE OF FOREIGN MATERIAL-CLEAN OR REPLACE 110-12 AND 110-14 3) BONDING DEVICE NEED BOTH SIDES SERVICE NIPPLES 250-94 4) MULTIPLE TERMINATIONS AT GROUNDING 5) TIGHTEN LOOSE FITTINGS AND USE APPROVED HARDWARE FOR SUPPORT-DRYALL SCREWS NOT APPROVED 6) BONDING JUMPER TO BE SIZED PER 250-102 AND 250-66 7) NEUTRAL TO BE BONDED AT SERVICE EQUIPMENT 8) LABEL PANELS 9) MAINTAIN DEDICATED WORK SPACE AT PANEL 110-26 10) SERVICE HAS BEEN ENGERGIZED WITHOUT CLEARANCE AND IS NOT CODE COMPLIANT AT THIS TIME 11) OUTSIDE LIGHTS TO COMPLY WITH LIGHTING ORDINANCE SECTION 5 12) TIGHTEN LOOSE SEAL TITE FITTINGS AND CONDUIT FITTINGS |