Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM00845
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 05/10/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CORRECTIONS NOT COMPLETED. HAVE WORK FINISHED PRIOR TO RECALLING |
|
| 05/06/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS OF WATER HEATER VENT CONNECTOR AND KITCHEN EXHAUST 2) PROVIDE ROOF JACKS AT GAS PIPE AND CONDENSATE PENETRATIONS THRU ROOF. BLOCK AND CLAMP CONDENSATE DRAIN LINE AND PAINT WITH LATEX PAINT 3) PROVIDE ELECTRIC DISCONNECTS FOR A/C UNITS. UNIT #8 FIREPLACE VENT MUST BE MINIMUM 3' ABOVE ROOF TO BOTTOM OF CAP 4) TIGHTEN FITTINGS ON GAS FLEX CONNECTORS |