Permit: T04CM00820

Parcel: 116026970

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T04CM00820

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/02/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/13/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) GROUND ALL METAL ELECTRIC BOXES 2) MAKE UP GROUNDS IN ELECTRIC BOXES 3) INSTALL NAIL PROTECTION ALL HOLES DRILLED INTO WOOD MEMEBERS 4) SECURE ROMEX WITHIN 12" OF ELECTRIC BOXES 5) INSTALL CEILING FAN ELECTRIC BOXES PER PLAN 6) BLOCK 3 SIDES MECH DUCTS AT CEILING 7) INSTALL ELECTRIC BOXES PER PLAN 8) INSTALL MECH DUCTS PER PLAN 9) PRIME AND WRAP ALL GAS PIPING JOINTS BELOW GROUND 10) COMLETE LATH 11) GAS PIPING HOLDING MINIMUM 10 POUND TEST OK 12) STOPPED INSPECTION. COMPLETE ALL FRAMING, ELECTRIC, PLUMBING MECH GAS AND RECALL WHEN READY