Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/09/2004 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
| 06/08/2004 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : Install 2 ground rods 6 feet apart with a continuous grounding electrode connection. Unable to determine which #4 cut is ufer. Install 2 ground rods 6' apart or provide proof that installed conductor is connected to ufer |
|
| 06/07/2004 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) INCOMPLETE, NO GROUNDING ? |
|
| 06/04/2004 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) ELECTRIC SERVICE NOT GROUNDED |
|