Permit: T04CM00791

Parcel: 10820099A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/21/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/08/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) NEED OUTLET 6' FROM NORTH DOUBLE DOORS 2) I.D. ALL WIRES BY COLOR IN PANELS 3) NEED 18" OF COVER NON/METALLIC CONDUIT, OR 2" CONCRETE 12" DEPTH 4) WIRING AT EXISTING BACK DOOR, BRING ALL J-BOXES FLUSH WITH FINISH WALL, HOT WIRE AT PLATE LINE ? 5) NEED TO HAVE TEP REMOVE OLD SERVICE LINE 6) OK TO START INSULATING