Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/22/2004 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/02/2004 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) HOT WATER HEATER NEEDS A TPR DRAIN PIPE TO THE EXTERIOR (HARD PIPE ONLY) 2) LAUNDRY DRAIN PIPE IS LOOSE 3) GFI LEFT OF STOVE IS MIS-WIRED 4) HALL BATH GFI IS LOOSE IN WALL 5) SEAL HALL TOILET TO FLOOR 6) HALL BATH VENT FAN IS INOPERABLE 7) MASTER BATH NORTH GFI IS MIS-WIRED AND LOOSE 8) NEED A SMOKE DETECTOR IN THE HALL WAY LEADING TO BEDROOMS 9) BASE BOARD CONTROL THERMOSTAT, IN NORTH EAST BEDROOM, APPEARS TO BE INSTALLED OIN THE WRONG LOCATION. PLEASE PROVIDE SPECS. REGARDING LOCATION OR MOVE THE CONTROLS 10) RAISE DISHWASHER DRAIN HOSE TO BOTTOM OF COUNTER 11) NEED HOUSE NUMBER |
| 02/25/2004 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) NO POWER YET |
| 02/23/2004 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |