Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/02/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MICROWAVE OUTLET NOT FINISHED 2) OUTSIDE LIGHT BY REAR DOOR MISSING 3) GFI OUTLET BY REAR DOOR MISSING 4) A/C DISCONNECT CANNOT BE BEHIND COMPRESSOR-NEEDS CLEARANCE PER NEC 110-26, #10 ROMEX BEHIND DISCONNECT NEED BUSHING FOR PROTECTION, TAPE WHITE WIRE BLACK STRAP 1/2 ? TO WALL 5) SERVICE HUB AT TOP OF PANEL SCREW IT DOWN WHERE IS WATER AND GAS BOND, WHAT IS GROUND WIRE TIED TOO ? SEAL 1/2 HOLE BOTTOM OF PANEL, OCVER TRENCH BE SERVICE FOR FINAL 6) LABEL SERVICE PERMANENTLY WITH ADDRESS |