Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/13/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :*/ 1) OK FINAL |
| 04/06/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NO ENTRANCE ABOVE DISCONNECTING MEANS IN ENTRANCE SECTION. 2) ENTRANCES ABOVE CURRENT CARRYING PARTS TO HAVE AN APPROVED SEALING DEVICE. 3) FUSE CONDUCTORS TO AMPACITY OF CABLE 336-26. 4) NM CABLE NOT TO BE INSTALLED IN A RACEWAY SYSTEM. 5) PROPERLY TERMINATE GROUNDING EQUIPMENT CONDUCTORS. 6) TIGHTEN LOOSE FITTINGS. 7) MAINTAIN WORKING CLEARANCE IN FRONT OF DISCONNECT. 8) SUPPORT M/C CABLE AS PER CODE IN ATTIC. |