Permit: T04CM00774

Parcel: 126100010


Addresses:

570 N COLUMBUS BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/13/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/ 1) OK FINAL
04/06/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) NO ENTRANCE ABOVE DISCONNECTING MEANS IN ENTRANCE SECTION. 2) ENTRANCES ABOVE CURRENT CARRYING PARTS TO HAVE AN APPROVED SEALING DEVICE. 3) FUSE CONDUCTORS TO AMPACITY OF CABLE 336-26. 4) NM CABLE NOT TO BE INSTALLED IN A RACEWAY SYSTEM. 5) PROPERLY TERMINATE GROUNDING EQUIPMENT CONDUCTORS. 6) TIGHTEN LOOSE FITTINGS. 7) MAINTAIN WORKING CLEARANCE IN FRONT OF DISCONNECT. 8) SUPPORT M/C CABLE AS PER CODE IN ATTIC.