Permit: T04CM00772

Parcel: 12511196A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/14/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/30/2004 ELECTRIC - INTERMEDIATE Partial Approval
04/16/2004 ELECTRIC - INTERMEDIATE Partial Approval PARTIAL OK
04/01/2004 ELECTRIC - INTERMEDIATE Partial Approval 1) BOXES TO HAVE BRACING SPEC'S 8F 2) SUPPORT M/C 3) WIRING IN EXAM 517.13 4) SUPPORT ? CABLES OR GRID
03/31/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) BOXES TO HAVE BACK BRACING AS PER SPECS 8F. 2) SUPPORT M/C CABLE AS PER 334 AND 300-11. 3) NOTE: ALL WIRING INCLUDING EXISTING IN EXAM ROOM TO BE AS PER 517-13. 4) VDV CABLES LAYING ON GRID PLEASE SUPPORT.