Permit: T04CM00738

Parcel: 10603167C

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Date Description Inspector Results Comments
05/26/2004 ELECTRIC - TEMP POWER FOR TEST Approved FOR A FINAL THE TWO GROUND ROD TOPS SHALL BE PROTECTED AGAINST PHSICAL DAMAGE AS PER 250-52, C-3 AND 250-10 OF 99 NEC. ALSO ALL GOT CONDUIT ENTRIES INTO PANELS TO HAVE BUSHING FOR ANY CONDUCTORS #4 OR ABOVE.