Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2004 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/04/2004 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) SOME FIXTURES ARE NOT SCREWED TO GRID 2) COILING MC CABLE AROUND TRUSSES IS NOT AN APPROVED METHOD OF SUPPORT. REMOVE WINDINGS AND SUPPORT FROM INDEPENDENT WIRES. SUPPORT WIRES MUST ALSO BE TIED TO GRID. RUNNING MC OVER TRUSS BOTTOM CORD IS OK, BUT DO NOT WIND. RECALL |