Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/08/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE GROUND CONTINOUS TO PANEL |
| 04/08/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 03/31/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*/1) MAST REQUIRES GUY STRUT IN DIRECTION OF SERVICE POLE 2) TWO 8' GROUND RODS REQUIRED AT LEAST 6' APART CONNECTED TO THE SERVICE PANEL WITH A CONTINOUS #4 CONDUCTOR OR CONTINOUS #6 CONDCUTOR WHICH IS FULLY PROTECTED FROM PHYSICAL DAMAGE 3) ADDRESS MUST BE ON SERVICE PANEL 4) 36" CLEARANCE REQUIRED IN FRONT OF ELECTRIC SERVICE PANEL |