Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM00691
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/29/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ OK FINAL. | |
03/26/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) APPROVED FITTINGS ARE NEEDED FOR M/C CABLE-NOT ROMEX 2) SUPPORT PANEL FEEDER JUNCTION BOX | |
03/23/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) BOXES NOT TO BE MORE THAN 1/4" IN NON COMBUSTIBLES-AN APPROVED EXTENDER RUN IS NEEDED-METAL IS NOT APPROVED 2) AN APPROVED FILLER BLANK IS NEEDED-NOT DUCT TAPE 3) MAINTAIN CLEARANCES IN FRONT OF PANEL 'B' 110.26 | |
02/27/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) APPROVE FOR 2 SOUTH |