Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM00686
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2005 | ELECTRIC - INTERMEDIATE | Approved | ||
04/12/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ BATHROOMS AND HALL WALL. / BE ADVISED: THE PLAN MAKES REFERENCE, ON SHEETS E3-E4, FOR THE USE OF CONDUIT (EMT?) IN WALLS ETC. THE WIRING METHOD USED IS METAL CLAD CABLE. THIS CHANGE MUST BE APPROVED BY THE ENGINEER OF RECORD, MR MARTIN S. ARMENTA. PLEASE REQUEST MR. ARMENTA TO ISSUE A STATEMENT ON HIS CO. LETTERHEAD APPROVING THE CHANGE. WITHOUT THE ENGINEERS CONSENT M.C. CABLE WILL HAVE TO BE REMOVED AND CONDUIT INSTALLED PER PLAN. |