Permit: T04CM00665

Parcel: 134080090


Addresses:

8432 E KENYON DR


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM00665

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
05/07/2004 FRAMING Approved IVRS - Inspection :
See detailed listing on site.| 999*/ 1) RE-INSPECT
05/06/2004 FRAMING Denied IVRS - Inspection :/ 1) MAKE UP (CONNECT) ALL GROUND WIRES IN ELECTRICAL BOXES AND SECURE WITH A MECHANICAL FASTENER 2) GROUND ALL METAL ELECTRICAL BOXES 3) PROVIDE A DWV WATER TEST OF PLUMBING VENTS AND DRAINS PER UPC 712.2. FILL TO ROOF 4) ELECTRIC SUB PANEL MUST BE GROUNDED AND HAVE AN ISOLATED NEUTRAL BAR 5) SHOWER CONTROL VALVE MUST BE TEMPERATURE/PRESSURE BALANCED ANTI-SCALD VALVE