Permit: T04CM00634

Parcel: 11623155D


Addresses:

633 W 18TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM00634

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/01/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. OUTSIDE LIGHT FIXTURES WHERE PAINTED BLACK ON THE ENTIRE INSIDE SURFACE OF LENS. USE APPROVED SHIELD BY MANUF.
2. GROUNDING ELECTRODE SYSTEM TO BOND TO BLD. STEEL IN AN APPROVED MANNER PER 250 NEC
3. NEW PANEL "R" TO BE ON PLAN ALONG WITH
SCHEDULE & DATA, BREAKER IN "L1" TO FEED PANEL "R" CALLS FOR 125 AMP NOT 100.
4. VERIFY SCH. 80 PVC FOR EXPOSED CONDUIT, IF NOT INSTALL SCH. 80
THE CONDUIT INSTALLED DOES NOT SPECIFY.
5. IF PVC IS TO BE USED, IT MUST BE 18" BELOW GRADE
PER 300.5 NEC

REVISE PLAN AS REQUESTED PER NOTE #5
LAST INSP. MUST BE APPROVED THRU PLAN CHECK.
PER NOTES #3 INSP 10/19/06 & NOTES THIS INSPECTION.
10/19/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES:
1. OUTSIDE LIGHT FIXTURES NOT PER PLAN.
2. GROUND ELECTRODE SYSTEM REQUIRED PER 250.32 NEC
SEPARATE BLD. FED FROM COMMON SERVICE.
3. NEW PANEL "R" NOT SHOWN ON ONE LINE DIAGRAM, NO SPEC'S ON PLAN, PLEASE ADDRESS THIS ARCH. NEED MORE INFO. MUST BE ON PLAN & APPROVED THRU PLAN CHECK.
4. PLANS CALL FOR RG'S OUTSIDE BLD. PVC MAY BE USED U.G ONLY.
5. PLANS CALL FOR FUSED HEAVY DUTY DISCONNECT FOR COOLER BLOWER?
6. INSTALL PER PLAN OR REVISE PLAN TO FIELD INSTALLATIONS.