Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/07/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 09/10/2004 | ELECTRIC - FINAL | Partial Approval | 1) REMOVE OR PROPELY TERMINATE ,OR PROPERLY SECURE CONTROL WIRING HANGING IN FROM TO TRANFER SW INSIDE GEAR. MAIN SW GEAR. 2) WOODEN FRAME NOT TO BE PLACED ON FRONT OF SW GEAR BOARD 3) PROVIDE REVISION FOR NEW PANEL CREP -2 INSTALLATION AND PANEL SCHEDULE FOR CIRCUITRY CREP-2 SHOWS ON PLAN BEING 200A FEED TO PNL. ON SITE IT IS A 600A FEED TO NEW PNL 4) CANNOT FIND ANY VERIFICATION OF EMPIRE GENERATOR HAVE A 3RD PARTY LISTING FROM A TESTING LAB PER NEC 1000 110-3 ( 500 KW GENERATOR)) |