Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/06/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/05/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ BLOCK LEFT IN GROUND IN FRONT OF SERVICE STILL VIOLATES CLEARANCE. THE LEVEL SHALL BE UNOBSTRUCTED 3FT AWAY. PLEASE READ 99 NEC. |
| 04/01/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 03/30/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ NO CHANGE FROM LAST INSP. DATED 3/18/04. A RE-INSPECTION FEE IS DUE PRIOR TO NEXT INSP. |
| 03/18/2004 |
ELECTRIC - FINAL |
|
Denied |
1) BLOCK WALL VIOLATES 3 FEET CLEARANCE REQUIRED IN FRONT OF SERVICE |
| 03/16/2004 |
ELECTRIC - FINAL |
|
Cancelled |
IVRS - Ri canceled |
| 02/10/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ ELECTRICAL PEDISTAL MUST BE RAISED TO 24" TO BOTTOM OF LOAD CENTER/METER COMBO. |