Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM00579
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/12/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*/ OK FOR FINAL C OF O. | |
03/10/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ 1) CAP OFF SECONDARY DRAIN AFTER TEE. PLUG UNUSED CONDENSATE OUTLETS 2) FAN COIL OVERFUSED. 15 AMP IS MAX. 3) SECURE REFER LINES TO WALL. PROVIDE PROTECTION FOR CONTROL WIRING 4) PERMANENTLY LABEL EQUIPMENT WITH ADDRESS 5) PROVIDE PROPER FUSES FOR CONDENSOR |