Permit: T04CM00562

Parcel: 141185820


Addresses:

10180 E RITA RD

Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Date Description Inspector Results Comments
08/18/2004 ELECTRIC - CONSTRUCTION POWER Approved IVRS - Inspection :*/APPROVED-OK TO CLEAR TEMP FOR CONST.
1. RON LARSON WCS ELECT-CONTRACTOR 358-0089
08/12/2004 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) UFER TIE TO ENCLOSURE ONLY - NEED A MAIN BONDING JUMPER TO NUETRAL. 2) ENCLOSURE INDICATES LINE SIDE CONDUCTORS AT TERM CAN TO BE LACED - SEE DRAWING. 3) GROUND WIRE CONNECTED TO BUSHINGS IN A DAISY CHAIN LOOP TOO SMALL CHECK NEC 250 ON EQUIPMENT GROUND SIZES. 4) INSTALL FUSING ON 100 AMP OWNERS SWITCH TO VERIFY FAULT CURRENT SIZE. 5) BACK FED 100 AMP CIRCUIT BREAKER ON OWNERS PANEL REQUIRED TO HAVE CLIP OR BOLT TO FRAME BECAUSE IT'S BACK FED. 6) REMOVE NUETRAL TO ENCLOSURE BOND IN OWNERS PANEL - THIS IS TO BE AN ISOLATED NUETRAL STRIP. 7) VERIFY SIZE AND INSULATION OF FEEDERS FROM TEP INTO TERM CAN - CANNOT READ INSULATION.