Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T04CM00554
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/28/2005 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) ALL CORRECTIONS HAVE BEEN MADE | |
01/21/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*1) SOIL WATER TEST IS OK. 2) ALL COLLECTIONS HAVE BEEN MADE. 3) SHALL PROVIDE A DIRECTIONAL FITTINGS FOR FLAT VENT @ TUB. 4) RE TEST SYSTEM. | |
01/18/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*PLEASE READ ALL NOTES, HAVE YOUR PLUMBER ON SITE FOR REINSPECTION. |
|
01/05/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER CLOSET VENT SHALL RISE VERTICAL FROM DRAIN. 2) CANNOT CONNECT A DRAIN INTO VENT FOR WATER CLOSET. 3) SHALL PROVIDE DBL FIXTURE FITTINGS FOR BACK TO BACK LAVATORIES. 4) RE VENT SAN TEE IS BACKWARDS BOTH UNITS 5) CANNOT LOCATE P-TRAP FOR WASHER BELOW GRADE OR HAVE EXPOSED ABS. 6) BLDG. SEWER SHALL HAVE MIN OF 12: OF COVER 7) STAND PIPE FOR WASHER @EAST UNIT MIN SHALL BE 18", 30" MAX. 8) CANNOT CONNECT WASHER DRAIN INTO TUB VENT. 9) CANNOT USE COMBO FOR TRAP ARM @ WATER CLOSET VENT AND THIS TRAP ARM SHALL BE?? |