Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2004 | FRAMING | Approved | IVRS - Inspection :* | |
| 06/15/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) FIREBLOCK IN GARAGE CHASE REQUIRES 2 LAYERS OF 1/2" 2) KITCHEN SHEAR WALL P-1 DAMAGED HAS 12 X 14 HOLE 3) 2ND FLOOR W/C PLUMBING REQUIRES 1/4" /FT PITCH 4) 2ND FLOOR CHASE REQUIRE 2 LAYERS OF 1/2" 5) SEAL FLOOR PENETRATION 6) SHEAR WALL REQUIRES STUDS AT 16" ON CENTER 7) 18A/SDE NOT COMPLIED WITH 8) STOPPED INSPECTION |
|
| 06/14/2004 | FRAMING | Partial Approval | IVRS - Inspection :*/ 1) FIRE BLOCK AT 2ND FLOOR AND 1ST FLOOR 2) A.B. LOOSE THRU-OUT |