Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T04CM00537
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/20/2004 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :*/ 1) WATER TEST THRU ROOF WASTE AND VENT OK 2) CLOSET FLANGES OK | |
09/16/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/H2O PIPING FROM TIE IN AT 2 1/2" TO TEST ROOM (EXC) ON WATER TEST H2O (ONLY) | |
09/15/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : 1) SUPPORT VENT PIPING PROPERLY WITH APPROVED CLAMPS AND PROVIDE AIR OR WATER TEST THRU ROOF. 2) H20 PIPING REQUIRES VERTICAL SUPPORT IN CHASE AND AIR OR WATER TEST. |
|
08/02/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) WATER TEST ON WASTE AND VENT TO ABOVE CEILING IN RESTROOM OK. 60 PSI AIR TEST ON H20 PIPING IN WALL OK 2) WILL NEED TO SEE 2" CW TIE INTO RESTROOM AREA BACK TO EXISTING PER PLAN 3) IF VENT IS OFF SET IT WILL REQUIRE A FUTURE WATER OR AIR TEST |