Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T04CM00535
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2004 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :*/APPROVED 1) SOIL WATER TEST IS OK 2) OVERHEAD WATER DISTRIBUTION IS OK 3) OK FOR DRY WALL |
|
| 08/25/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) SOIL WATER TEST IS OK FOR UNIT #132 ONLY 2) SHALL REMOVE ALL CLEANOUTS, TEES NOT REQUIRED OR ACCESSIBLE 3) RETEST SYSTEM | |
| 08/19/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) CANNOT LOCATE ANY THREADED FITTINGS IN A NON-ACCESSIBLE LOCATION SEE SECTION 316.1.5 94 UPC INSTALLATION STANDARDS 2) SHALL PROVIDE A DIRECTIONAL FITTING WHEN EXTENDING CLEANOUT SEE SECTION 707.7 94 UPC 3) SHALL PROVIDE NON CORROSIVE SCREW FOR CLOSET FLANGES 4) SHALL SECURE ALL HORIZONTAL VENTS THRU ROOF |