Permit: T04CM00533

Parcel: 12413011A

Inspection Status: Approved

Inspection History: PLUMBING - ROOF DRAINS

Permit Number - T04CM00533

Inspection Description - PLUMBING - ROOF DRAINS

Inspection Status - Approved

Date Description Inspector Results Comments
02/22/2005 PLUMBING - ROOF DRAINS Approved IVRS - Inspection :* APPROVED
07/13/2004 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*/ 1) 6" BLDG SEWER STUBBED 2' OUTSIDE BLDG 6" BLDG DRAIN UNDERGROUND BACK TO WASTE AND VENT ONLY FOR 110, 111, 112, 113, 114, 115, 116, 111B, 113B AND 115B WATER TEST OK 2) NEED TO SEE 2-WAY BLDG CLEANOUT INSTALLATION 3) 6" RWL + 4" RWL UNDERGROUND WATER TEST TO 2" OUTSIDE BLDG BETWEEN CENTER LINE 6+7 AND SOUTH OF UNIT 111 OK 4) 4" RWL UNDERGROUND WATER TEST TO 2' OUTSIDE BLDG BETWEEN CENTER LINE 8+11 SOUTH OF 113+115 OK
06/25/2004 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
06/24/2004 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*/ 1) SOIL WTR TEST FOR ISLAND VENTING AT COLUMN #20.4 IS OK. 2) SOIL WTR TEST FOR 4" AND 6" AREA DRAINS AND RWL IS OK FOR BLDG 'A' EAST AND BLDG 'B' AS NOTED ON PLAN. 3) 1½" WTR SERVICE BLDG 'B' IS OK.