Permit: T04CM00531

Parcel: 13313006K


Addresses:

7649 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM00531

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/12/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/ OK FINAL
05/10/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) RECEPTACLES IN BATHROOM TO BE GFCI 210.8 2) WATER HEATER TO HAVE DISCONNECTING MEANS 3) FILL UNUSED OPENINGS IN PANEL-REVISE PANEL SCHEDULES AS TO PLANS 4) ROOF: SUPPORT SEAL TIGHT AND TIGHTEN LOOSE FITTINGS 5) PROTECT FROM SHARP METAL EDGES 6) GROUND JUNCTION BOXES PER CODE 250.148 7) FILL UNUSE OPENINGS IN JUNCTION BOX
04/12/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ NO WORK PROGRESS - UNEECESSARY INSPS. CALLS MAY RESULT IN A RE-FEE.