Permit: T04CM00531

Parcel: 13313006K


Addresses:

7649 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/09/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
03/31/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) BOX CLAMPS NOT TO BE CUT OFF. 370-17. 2) BRING CEILING JUNCTION BOX DOWN FOR REQUIREMENTS OF 370-20. 3) PLEASE PROVIDE A LADDER FOR ACCESS TO DO ABOVE CEILING INSP. 4) GROUND METAL JUNCTION BOXES.
03/19/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999* 1) 32 CUBIC " 2 GANG BOX IS TOO SMALL AT EAST RESTROOM 2.25 C.I. PER CONDUCTOR & DEVICES . 2) ALSO YOUR CONDUCTORS ARE TOO SHORT NEED MIN 6" OF CONDUCTORS AT EACH BOX
03/17/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ FINISH INSTALLING ELECTRIC - SUPPORT AS PER CODES.