Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/09/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 03/31/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) BOX CLAMPS NOT TO BE CUT OFF. 370-17. 2) BRING CEILING JUNCTION BOX DOWN FOR REQUIREMENTS OF 370-20. 3) PLEASE PROVIDE A LADDER FOR ACCESS TO DO ABOVE CEILING INSP. 4) GROUND METAL JUNCTION BOXES. |
| 03/19/2004 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* 1) 32 CUBIC " 2 GANG BOX IS TOO SMALL AT EAST RESTROOM 2.25 C.I. PER CONDUCTOR & DEVICES . 2) ALSO YOUR CONDUCTORS ARE TOO SHORT NEED MIN 6" OF CONDUCTORS AT EACH BOX |
| 03/17/2004 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ FINISH INSTALLING ELECTRIC - SUPPORT AS PER CODES. |