Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/26/2004 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection :*/ CORRECTION MADE OK. |
| 05/24/2004 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) CLEAN-OUT TEE USED AS DRAINAGE FITTING AT URINAL NOT APPROVED 2) WHERE A VENT CONNECTS TO A HORIZONTAL DRAIN LINE IT SHALL HAVE IT'S INVERT TAKEN OFF ABOVE THE DRAINAGE CENTER LINE, DOWN STREAM OF THE TRAP BEING SERVED |
| 05/24/2004 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection :*/ 1) GREASE TRAP OK - NEXT TIME TRY AND GET YOUR VENT INVERT A LITTLE HIGHER. OK TO COVER. 2) AT URINAL - A SANTEE MAY ONLY BE INSTALLED IN THE VERTICAL POSITION FOR DRAINAGE PIPING. I'M CONCERNED ABOUT EXISTING PIPING NOT BEING WTR TIGHT - PLEASE TEST. |
| 04/28/2004 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection :*/ 1) ROUGH FOR KITCHEN OK SUBJECT TO REVISED APPROVED PLAN 2) OK TO COVER |
| 04/08/2004 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) YOU WILL POST YOUR ADDRESS WHERE IT CAN BE READILY SEEN FROM ST. MARYS RD. !!! 2) YOU MUST HAVE PERMIT AND INSPECTION HISTORY ON JOB SITE AT ALL TIMES. 3) IT IS YOUR RESPONSIBILITY TO MAKE SURE THE WORK IS READY BEFORE CALLING INSPECTION. 4) HAVE YARDWTR 03040 ADDED TO PERMIT BY NEXT INSP. |