Permit: T04CM00498

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
05/26/2004 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*/ CORRECTION MADE OK.
05/24/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*/ 1) CLEAN-OUT TEE USED AS DRAINAGE FITTING AT URINAL NOT APPROVED 2) WHERE A VENT CONNECTS TO A HORIZONTAL DRAIN LINE IT SHALL HAVE IT'S INVERT TAKEN OFF ABOVE THE DRAINAGE CENTER LINE, DOWN STREAM OF THE TRAP BEING SERVED
05/24/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/ 1) GREASE TRAP OK - NEXT TIME TRY AND GET YOUR VENT INVERT A LITTLE HIGHER. OK TO COVER. 2) AT URINAL - A SANTEE MAY ONLY BE INSTALLED IN THE VERTICAL POSITION FOR DRAINAGE PIPING. I'M CONCERNED ABOUT EXISTING PIPING NOT BEING WTR TIGHT - PLEASE TEST.
04/28/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/ 1) ROUGH FOR KITCHEN OK SUBJECT TO REVISED APPROVED PLAN 2) OK TO COVER
04/08/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*/ 1) YOU WILL POST YOUR ADDRESS WHERE IT CAN BE READILY SEEN FROM ST. MARYS RD. !!! 2) YOU MUST HAVE PERMIT AND INSPECTION HISTORY ON JOB SITE AT ALL TIMES. 3) IT IS YOUR RESPONSIBILITY TO MAKE SURE THE WORK IS READY BEFORE CALLING INSPECTION. 4) HAVE YARDWTR 03040 ADDED TO PERMIT BY NEXT INSP.