Permit: T04CM00497

Parcel: 10602249A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T04CM00497

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/29/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/23/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ WALLS APPROVED. PROTECT CABLE TO 1¼" MAKE UP GROUND WIRES. SUPPORT MC WITHIN 12" BOX
06/22/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ NEED CABLE PROTECTION IN AREA WHERE M/C IS CLOSER THAN 1¼ FROM EDGE OF STALL WHERE SCREW MAY PENETRATE. NEED GROUND WIRES/SCREW MAKE-UP. SUPPORT M/C WITHIN 12" OF BOX. DO PER MIN. CODE.