Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2004 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 05/28/2004 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PLAN SHOWS GUEST HOUSE TO HAVE A SEPERATE SERVICE FROM MAIN HOUSE. PRESENTLY WIRED AS A SUB PANEL FROM MAIN HOUSE WITH ONLY ONE MAIN PANEL. SUB PANEL IS WIRED INCORRECTLY. IT MUST BE WIRED WITH AN ISOLATED NEUTRAL BAR AND A GROUNDED GROUND BAR 2) NEW ? METER ADDED TO EXISTING HOUSE. HAVE PLAN REVISED AN APPROVED BY CITY FOR ASBUILT |