Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date |
Description |
Inspector |
Results |
Comments |
| 03/19/2004 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Approved |
IVRS - Inspection 0000* |
| 03/16/2004 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
IVRS - Inspection 0999*/ 1) PLUMBING CANNOT BE PARALLEL IN FOOTING 2) CMU SUPPORTING STEEL DISPLACES TOO MUCH CONCRETE 3) 1 1/2" CLEARANCE REQUIRED AT STEEL TO WASTE LINES, FORMS 4) 3" MINIMUM CLEARANCE AT STEEL TO SOIL 5) WRAP ALL EXPOSED WASTE (WHERE CONCRETE WILL CONTACT IT) 6) 1/4" PER FOOT SLOPE REQUIRED AT ALL WASTE 7) EXISTING STRUCTURE TO NORTH DOES NOT SHOW ON SITE PLAN. REVISE AND SUBMIT FOR APPROVED 8) NOT THE CARPORT-THE OTHER BLDG |