Permit: T04CM00393

Parcel: 141014440

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM00393

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
04/07/2004 FRAMING Approved IVRS - Inspection 0000*
04/02/2004 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) FIX ROMEX REAR BEDROOM, AT H.D. 2) NEED 1" CLEAR AT FIRE PLACE FLUE TO COMBUSTIBLES, INSTALL METAL FIRE STOP AT LOWER OSB PENETRATION 3) USE 1/2" CONDUIT AT ISLAND FLOOR CHASE, NEED CORRECT MATERIAL AND CORRECT CONC. COVER
04/01/2004 FRAMING Partial Approval 1) NEED DWV 2) ONE H.D. RETRO 3) AB'S 4) OK TO INSULATE