Permit: T04CM00367

Parcel: 110055480

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
03/03/2004 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*/ NEED TO SEE RELOCATED DUCT SMOKE DETECTORS. LEAVE OUT CEILING TILES IN THESE AREAS. WILL CHECK ON FINAL.
03/02/2004 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection 0999*/ 1) THE AIR SENSING TUBE FROM THE SMOKE DETECTORS MUST BE ABOVE BOTH INLETS ON THE RETURN PLENIUM. 2) SEAL THE JOINTS ON THE RETURN DUCT FOR HP-2. 3) SUPPLY DIFFUSER MISSING FROM HALLWAY. RECALL FOR INSPECTION.
02/13/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ INSPECTED SUSPENDED ROUGH DUCT. CHECKED CONDENSATE DRAIN IN WALL. INSPECTED SUPPLY AND EXHAUST TO RESTROOMS. OK TO SHEET ROCK.