Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/03/2004 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*/ NEED TO SEE RELOCATED DUCT SMOKE DETECTORS. LEAVE OUT CEILING TILES IN THESE AREAS. WILL CHECK ON FINAL. |
| 03/02/2004 |
MECHANICAL - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*/ 1) THE AIR SENSING TUBE FROM THE SMOKE DETECTORS MUST BE ABOVE BOTH INLETS ON THE RETURN PLENIUM. 2) SEAL THE JOINTS ON THE RETURN DUCT FOR HP-2. 3) SUPPLY DIFFUSER MISSING FROM HALLWAY. RECALL FOR INSPECTION. |
| 02/13/2004 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ INSPECTED SUSPENDED ROUGH DUCT. CHECKED CONDENSATE DRAIN IN WALL. INSPECTED SUPPLY AND EXHAUST TO RESTROOMS. OK TO SHEET ROCK. |