Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
11/19/2004 FRAMING Approved IVRS - Inspection :*
11/18/2004 FRAMING Partial Approval IVRS - Inspection :*
11/17/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/15/2004 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*/ 1) OUTSIDE ELECTRIC BOXES NOT WIRED
2) GROUND ALL METAL ELECTRIC BOXES
3) NO TRUSS DRAWINGS ON SITE
4) PROVIDE ENGINEERS APPROVED TRUSS REPAIR DOCUMENTS
5) CANNOT DETERMINE REPAIRED TRUSSES FROM 11/01/04
6) EAST FURNACE "B" VENT REQUIRES 1" TO COMBUSTIBLES
7) NO DWV WATER TEST
8) NO POTABLE WATER PRESSURE TEST
9) NAIL PROTECT W/H T & P LINE
10) SUPPORT 4 SWITCH-ELECTRIC BOXES TWO ENDS
11) NO GAS TEST
12) GAS LINE DOES NOT EXTEND INTO FIRE PLACE
13) STOPPED INSPECTION, TO MANY ITEMS
10/26/2004 FRAMING Not ready for Inspection IVRS - Inspection :*/ 1) TRUSSES INSTALLED NOT THE SAME CONFIGURATION AS TRUSS IN CALC'S, SEE VERT. MEMBER AT RIDGE, ALSO BEARING PTS. NOT SHOWN ONLY REATION AND WT. FB14-17 2) USE 16D COMMON NAILS IN ALL AHBUS 26 1 26-2 HANGERS 4) HAVE TRUSS CO REPLACE GUSSET PLATES ON TWO TRUSSES 5) SPENT OVER 1 HOUR GOING THRU TRUSSES HANGERS AND BEARING PTS., PLEASE RECALL INTER. FOR THE 27TH. I HAVE TO GO TO NEXT INSPECTION