Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2004 | FRAMING | Approved | IVRS - Inspection :* | |
| 11/18/2004 | FRAMING | Partial Approval | IVRS - Inspection :* | |
| 11/17/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/15/2004 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950*/ 1) OUTSIDE ELECTRIC BOXES NOT WIRED 2) GROUND ALL METAL ELECTRIC BOXES 3) NO TRUSS DRAWINGS ON SITE 4) PROVIDE ENGINEERS APPROVED TRUSS REPAIR DOCUMENTS 5) CANNOT DETERMINE REPAIRED TRUSSES FROM 11/01/04 6) EAST FURNACE "B" VENT REQUIRES 1" TO COMBUSTIBLES 7) NO DWV WATER TEST 8) NO POTABLE WATER PRESSURE TEST 9) NAIL PROTECT W/H T & P LINE 10) SUPPORT 4 SWITCH-ELECTRIC BOXES TWO ENDS 11) NO GAS TEST 12) GAS LINE DOES NOT EXTEND INTO FIRE PLACE 13) STOPPED INSPECTION, TO MANY ITEMS |
|
| 10/26/2004 | FRAMING | Not ready for Inspection | IVRS - Inspection :*/ 1) TRUSSES INSTALLED NOT THE SAME CONFIGURATION AS TRUSS IN CALC'S, SEE VERT. MEMBER AT RIDGE, ALSO BEARING PTS. NOT SHOWN ONLY REATION AND WT. FB14-17 2) USE 16D COMMON NAILS IN ALL AHBUS 26 1 26-2 HANGERS 4) HAVE TRUSS CO REPLACE GUSSET PLATES ON TWO TRUSSES 5) SPENT OVER 1 HOUR GOING THRU TRUSSES HANGERS AND BEARING PTS., PLEASE RECALL INTER. FOR THE 27TH. I HAVE TO GO TO NEXT INSPECTION |