Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
11/19/2004 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
11/01/2004 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*/ 1) TWO GIRDER TRUSSES STILL NEED NAIL REPLACEMENT GARAGE, AND FRONT ROOM, OFFICE 2) NEED TRUSS GUSSETS ON TWO TRUSSES, LEFT OFF AT PLANT 3) GAS PRESSURE-OK
10/22/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) PORCH POST/BEAM CALLS FOR 18" STRAPS 2) NEED TRUSS DRAWINGS ON SITE, TO VERIFY ALL 3PT BEARING PTS. SHIM WHERE NEEDED 3) TRUSS AT LARGE REAR DOOR OPENING MISSING METAL GUSSET PLATE BOTH SIDES OF JOINT4) BOL-GJ8 GIRDER USE CORRECT NAILS IN HANGER, HANGER SIZE NOT ON PLAN-F01-D03 NO HANGER SPECP, MISSING NAILS, CHECK TRUSS LAYOUT 5) MISSING HANGER ON TRUSS TO GIRDER NORTH OF KITCHEN COUNTER PENINSULA 6) 2ND GUSSET MISSING NORTH OF SAME COUNTER LOOK FOR MARKS ON FLOOR 7) FRONT ENTRY NEED HANGERS ON HIP JOINTS ANIL OFF TRUSS TOP CHORD, SOME HAVE 1 TOE NAIL, NO HANGER 8) DON'T LOAD ROOF
10/15/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) SHEAR WALLS #6 REQUIRE 4" EDGE NAILED 2) TWO HOLD DOWNS MISSING VACCUM