Permit: T04CM00356

Parcel: 135112050

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
01/19/2005 FRAMING Approved
07/14/2004 FRAMING Partial Approval IVRS - Inspection :*/ 1) SIDING NOT INSTALLED
06/24/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) WIRE AT TOP OF NORTH WALL MUST GO THROUGH THE HOLE IN THE RAFTER, NOT THE WALL 2) WIRE AT SOUTH WALL SWITCH MUS BE SECURED (STAPLED) WITHIN 6" OF SWITCH BOX 3) PUT PROTECTION PLATE ON TOP PLATE WHERE WIRE IS CLOSER TO THE FACE OF THE TOP PLATE, THAN 1 1/4" INCHES 4) NOTE: FRAME DOES NOT PASS UNTIL ELECTRIC PASSES
06/21/2004 FRAMING Denied IVRS - Inspection :
There is no plan or job inspection card on site.| 925*. No inspection can be done without approved plans.
04/15/2004 FRAMING Denied IVRS - Inspection 0999*/ 1) NEED PLAN ON SITE TO PERFORM INSPECTION 2) FRAME INSPECTION DOES NOT PASS UNTIL ELECTRIC INTERMEDIATE INSPECTION PASSES 3) BOTTOM WALL PLATES, IN CONTACT WITH CONCRETE, MUST BE PRESSURE TREATED