Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2005 | FRAMING | Approved | ||
| 07/14/2004 | FRAMING | Partial Approval | IVRS - Inspection :*/ 1) SIDING NOT INSTALLED | |
| 06/24/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) WIRE AT TOP OF NORTH WALL MUST GO THROUGH THE HOLE IN THE RAFTER, NOT THE WALL 2) WIRE AT SOUTH WALL SWITCH MUS BE SECURED (STAPLED) WITHIN 6" OF SWITCH BOX 3) PUT PROTECTION PLATE ON TOP PLATE WHERE WIRE IS CLOSER TO THE FACE OF THE TOP PLATE, THAN 1 1/4" INCHES 4) NOTE: FRAME DOES NOT PASS UNTIL ELECTRIC PASSES |
|
| 06/21/2004 | FRAMING | Denied | IVRS - Inspection : There is no plan or job inspection card on site.| 925*. No inspection can be done without approved plans. |
|
| 04/15/2004 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) NEED PLAN ON SITE TO PERFORM INSPECTION 2) FRAME INSPECTION DOES NOT PASS UNTIL ELECTRIC INTERMEDIATE INSPECTION PASSES 3) BOTTOM WALL PLATES, IN CONTACT WITH CONCRETE, MUST BE PRESSURE TREATED |