Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM00346
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/08/2004 | ELECTRIC - FINAL | Approved | OK PER DAVE MANN AT PERMIT COUNTER | |
06/29/2004 | ELECTRIC - FINAL | Denied | FIXTURE IS NOT LISTED AS A WHOLE ASSEMBLY. CORD ALONE MAY BE LISTED - THE WHOLE TYPE FIXTURE MUST BE LISTED AS A UNIT. | |
05/19/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ SEE LETTER FROM ENGINEER. - OK FOR CONDITIONAL TEMP C OF O. | |
05/14/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ OK TO PREPARE FOR BUSINESS W/O PUBLIC ACCESS. NEC 400-8 (1) - USES PERMITTED FOR CORD. NEC 410-15 - SUPPORT OF FIXTURES. PLEASE REFER THIS PROBLEM TO THE ENGINEER OF RECORD. | |
05/10/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COOLER IN PANEL MISSING -CIRCUITS APPEAR AS PER PLA. 2. INTAKE FAN INTERLOCK DIAGRAM ON PLAN NOT INSTALLED. 3. RECEPTACLE BEHIND MIRROR TO BE CUT OUT. 4. C-23 WP RECEP NOT MADE UP OR BLACKED. 5. OPEN J-BOX CEILIN. 6. WATER HEATER SHOW A DISCONNECT BY IT ON PLAN. 7. HOW IS FAN INTERLOCK ACCOMPLISHED, AS REQUIRED PER PLAN. 8. FIXTURES INCEILING DROPPED BY CORD NED TO BE OF A IISTED TYPE. 9. PLAN SHOW NEW 200A DISCONNECT WITH 125A FUSES TO FEED PNL C. |