Permit: T04CM00341

Parcel: 10511040A


Addresses:

4380 N ORACLE RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
04/27/2005 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :* 1) CORRECTION MADE OK OK FOR CONCRETE
04/26/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) WORK COVERED WITHOUT RE-INSPECTION
2) MIKE-DO NOT POUR CONCRETE UNTIL YOU EXPOSE DBL FIXTURE FITTING FOR BACK TO BACK FLOOR DRAINS, AND HAVE IT INSPECTED
04/25/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :* 1) NOT READY FOR INSPECTION
04/22/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) AS WE DISUSSED, A DBL WYE WITH AN EIGHTH BEND PUTS THE POINT OF VENT BELOW THE TRAP WEIR ON ALL FIXTURES EXCEPT WATER CLOSET. USE 3" DBL FIXTURE FITTING AT P-11'S
2) OK TO COVER THE REST