Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T04CM00332
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/01/2004 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
10/27/2004 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The conduit is not installed per code.| 240*/1)DEPTH OF PVC MUST BE MIN. 18" TOP OF CONDUIT TO GRADE LEVEL |
|
10/13/2004 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 4" PVC FROM CT CAN TO TEP TFMR. | |
09/14/2004 | ELECTRIC - UNDERGROUND | Partial Approval | 1)OK TO COVER ALL ELECT UNDERGROUND WITHIN BODG. 2)OK TO COVER 4" PVC NORTH WALL BLDG TO MAIN DISCON. | |
09/13/2004 | ELECTRIC - UNDERGROUND | Cancelled | ||
09/13/2004 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* |