Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2004 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 07/21/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) POST ADDRESS ON 35 TH ST. SIDE OF HOUSE 2) OUTSIDE HOSE BIB REQUIRES ANTI-SIPHON VALVE 3) OUTLET FOR DISH WASHER MUST BE READILY ACCESSIBLE 4) INSTALL RANGE GAS VALVE AND CAP 5) CAULK TUB AND TOILET 6) BATHROOM GFCI HOT WHEN TRIPPED 7) BEDROOM WINDOW SECURITY BARS MSUT BE READILY REMOVABLE 8) SMOKE DETECTOR IN BEDROOM INOPERABLE 9) LABEL ALLL CIRCUITS IN ELECTRIC PANEL 10) DIELECTRIC GREASE REQUIRED ON ELECTRIC ALUMINUM |
|
| 07/19/2004 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/03/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |