Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T04CM00287
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/31/2004 | PLUMBING - FINAL | Approved | OK FOR C OF O | |
03/30/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/ 1) PVC SCH 40 IS NOT APPROVED WITHIN STRUCTURE AT BACKFLOW PREVENTORS. 2) MUST PROVIDE VACUUM BREAKER AT HOSE BIB. 3) MUST COVER VENT FOR GREASE TRAP. 4) MUST PROVIDE BACKFLOW PREVENTION FOR EACH CARBONATED WATER. | |
03/29/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/ TRAP MUST BE THE SAME SIZE AS THE DRAIN IT SERVES. SEE SECTION 1003.3 94 UPC. | |
03/26/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/ 1) TRAP SEAL CANNOT BE MORE THAN 4" OR LESS THAN 2" SEE SECTION 1005.0 94 UPC. | |
03/23/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/ 1) MUST USE A APPROVED STRAP FOR INDIRECT WASTE FOR PEEP SINK 2) MUST USE A DIRECTIONAL FITTING IN LIEU OF SAN-TEE FOR TRIPLE COMPT. SINK SEE 405.494' UPC 3) MUST CAULK ALL FIXTURES 4) MUST PERM MARK OR STICKER FOR ANZUL VALVE LOCATION PRIOR TO FINAL INSPECTION 5) SOIL WATER TEST IS OK |