Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2004 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 05/04/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) CONDENSOR NOT LEVEL 2) SMOKE DETECTORS MISSING 4 EACH 3) GAS LINE MUST BE 36' AWAY FROM OPENABLE WINDOW 4) CLEAN FAU SECONDARY PAN 5) PROVIDE 1" CLEARANCE FROM COMBUSTIBLES AT B-VENT ATTIC (FAU) |