Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM00264
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/22/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/OK FOR FINAL C/O | |
11/18/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/DUCT DETECTORS STILL NOT WORKING |
|
11/16/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/DUCT SMOKE DETECTORS NOT SHUTTING OFF THE EQUIPMENT. CAP OFF THE VENT UPSTREAM OF THE CONDENSATE TRAP. AC-1 REPAIR ELEC. DISCONNECT-LEVER NOT ENGAGING AC-2. REPAIR LOOSE CONDUIT TO DISCONNECT AC-1. REPAIR CONNECTION TO J-BOX AC-1 |
|
11/03/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*/OK FOR TEMP C/O FOR SETTING UP & STOCKING ONLY. NEED TO TEST DUCT SMOKE DETECTORS & CHECK EQUIPMENT ON ROOF | |
11/01/2004 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :*/NEED TO TEST DUCT SMOKE DETECTORS. NEED TO SEE FRESH AIR INTAKES. |