Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM00249
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/17/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
05/13/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*/ 1) PLEASE PROVIDE PROPER SIZE FILTERS IN A/C UNITS. 2) PROVIDE A MANUAL DAMPER IN OUTSIDE AIR INTAKE. 3) PROVIDE LISTING ON DUCT SMOKE DETECTORS. | |
05/11/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
05/06/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ DUCT SMOKE DETECTORS WERE DRAWN IN ERROR ON PLANS. DETECTORS TO BE INSTALLED IN THE RETURN DUCTS. MARK UNIT DATA PLATES WITH PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY. OK FOR TEMP C OF O. |