Permit: T04CM00249

Parcel: 121016260


Addresses:

1951 N WILMOT RD 01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/13/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/ OK FINAL.
05/11/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ NEED TO SEE WTR HTR CONNECTIONS. OK TEMP C OF O.
05/07/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :
See detailed listing on site.| 999* 1) SUPPORT VDV CABLES UP OFF OF GRID 2) MAINTAIN WORKING CLEARANCES IN FRONT OF PANELS 3) FILL UNUSED OPENINGS IN WATER HEATER 4) WE HAVE EXTRA CONDUCTORS W/ A/C DISCONNECT NOT FOR ANY PURPOSE, PLEASE REMOVE. * TREATMENT ROOM NOT USED AS PATIENT CARE AREAS, USE FOR SLEEP MONITORING ONLY.
sERVICE IS EXISTING 1600 AMP SERVICE WITHOUT 2ND EXIT AS PER 110-26
05/06/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) CANCELLED BY CONTRACTOR