Permit: T04CM00233

Parcel: 11445262J

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM00233

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/08/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/05/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* 1) LABEL ON UNITS STATE 30 AMPS WE HAVE MORE THAN 3 CONDUCTORS IN CONDUIT WITH #10 WIRE. DUE TO ? THE CONDUCTOR CAPACITY IS NOT LARGE ENOUGH FOR STATED LOADS. CHECK WITH MANUFACTURER AND UNIT ONLY. DRAWS 18.5 AMP 2) PLANS CALL FOR 40MAP & # 6 CONDUCTORS.PLEASE REVISE PLANS. OK FOR TEMP C OF O.
03/01/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) OK SERVICE #2 AND 3 PREVIOUS INSPECTION 2) WAITING ON EQUIPEMENT 3) PLEASE TIGHTEN CORD CONNECTOR, PROTECT AND SECURE CORD TO JUNTION BOX
02/11/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) NEED TO SEE EQUIPMENT TO VERIFY DERATING OF CONDUCTORS AND LISTING LABELS. 2) NEW DISCONNECT NOT TO BE HIGHER THAN 6'7" TO CENTER OF HANDLE 380-8. 3) LINE SIDE BONDING JUMPER TO BE SIZED PER 250-102 AND 250-66.