Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T04CM00225
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/14/2004 | FRAMING | Approved | IVRS - Inspection 0000* | |
| 04/13/2004 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) FILL IN GAPS UNDER HEADERS AND GAPS AT CUT STUDS TO CORRECT BOWED STUDS 2) MAINTAIN MINIMUM 1" CLEARANCE TYPE B-VENT TO COMBUSTIBLES (PUTTING SHEET METAL ON WOOD DOES NOT WORK) 3) INSTALL H2.5 BLOCK TO BOTTOM CHORD TRUSS PER DETAIL 2/SD2 | |
| 04/09/2004 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) REPLACE MISSING FIREBLOCKS 2) FILL IN SOLIDLY GAPS UNDER HEADER AT BEARING 3) 1" CLEARANCE FLUE PIPE TO COMBUSTIBLES 4) BLOCKING MISSIN SEE DETAIL 2-SD/2 5) NAIL OFF LOOSE COIL STRAP GARAGE CEILING 5) STRAP BEAMS/HEADERS TO BEARING POINTS | |
| 04/01/2004 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) INSTALL BANG PLATE PROTECTION ALL PLUMBING AND ELECTRIC 2) WRONG NAILS USED HANGERS; FILL ALL HOLES HANGERS 3) SECURE GAS LINE THROUGHOUT 4) NO WATER TEST DWV 5) NOT EVEN CLOSE 6) STOPPED INSPECTION |